4Ć170
Target Data Configuration
Original Ć June 1990CE4.2:CL6211
4.7 Target Data Configuration
4.7.1 Target Data Configuration Items
The TARGET DATA form is used to define items related to targeting a
point to other PROVOX devices. Refer to section NO TAG (page
NO TAG) for additional information relating to targeting points. Refer to
Using ENVOX Configuration Software UM4.14:SW3151 for instructions on
creating target groups.
There are additional parameters that must be specified when targeting
this point to UOC, TREND, and PROVUE devices. These additional
forms are accessed from the EXTRA DATA menu option.
Alarm Display Ċ Indicates if an alarm display is to be configured for this
point. YES indicates an alarm display will be configured, NO indicates an
alarm display will not be configured. If no alarm display is configured,
the system will use the configured detail display.
Alarm Display Identifies the specific display that is to appear when
an operator selects this point. The display must be in the display list of
all the PROVUE consoles that the point is being targeted to.
Alarm Group A Ċ Identifies the number of the alarm group to which the
A alarm for this point is assigned. This will determine how this particular
alarm is handled and its priority level. Valid range for this value is 1 to 7
for P4.1 and earlier PROVUE consoles, or 0 to 7 for P5.0 and later
versions.
Alarm Group B Ċ Identifies the number of the alarm group to which the
B alarm for this point is assigned. This will determine how this particular
alarm is handled and its priority level. Valid range for this value is 1 to 7
for P4.1 and earlier PROVUE consoles, or 0 to 7 for P5.0 and later
versions.
Alarm Group C Ċ Identifies the number of the alarm group to which the
C alarm for this point is assigned. This will determine how this particular
alarm is handled and its priority level. Valid range for this value is 1 to 7
for P4.1 and earlier PROVUE consoles, or 0 to 7 for P5.0 and later
versions.
Alarm Group D Ċ Identifies the number of the alarm group to which the
D alarm for this point is assigned. This will determine how this particular
alarm is handled and its priority level. Valid range for this value is 1 to 7
for P4.1 and earlier PROVUE consoles, or 0 to 7 for P5.0 and later
versions.