4Ć69FST Configuration
Original Ć June 1990 CE4.2:CL6211
DTC DTC
(Continued from previous page)
CONFIGURATION FORMAT: DTC (
Process gain >>
Process time constant >>
Process dead time >>
Reset >>
Comment >>
OPERAND DESCRIPTIONS:
Process gain - A tuning parameter that specifies the proportional relationship of the process
variable (PV) and the valve output (VO). Gain = (
DPV) / (D VO). Gain values are 0, or 0.003906 to
127.996.
Process time constant - A tuning parameter that specifies the first order filter, where the time for
the process variable to change is 63.2 percent of the change in valve output minus the transport
delay. Time constant values are: 0, or 0.0042 to 134.23 minutes for the 4 hertz version controller; 0,
or 0.0017 to 53.69 minutes for the 10 hertz version controller; and 0, or 0.0009 to 26.84 minutes for
the 20 hertz version controller.
Process dead time - A tuning parameter that is equal to the actual "transport delay" of the
process in minutes. Dead time values are: 0, or 0.0644 to 2109.85 minutes for the 4 hertz version
controller; 0, or 0.0258 to 843.94 minutes for the 10 hertz version controller; and 0, or 0.0129 to
421.97 minutes for the 20 hertz version controller.
Reset - The name of the general register or discrete loadable function that contains the discrete
value used to reset the DTC function (0 = enabled, 1 = reset).
Comment - A comment up to 255 characters long.
CONFIGURATION EXAMPLE:
FUNCTION EQUATIONS:
SVA(out) = SVA(in)
SVD(out) = SVD(in)