Response Electronics CL6011B Spezifikationen Seite 133

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 320
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 132
4Ć51FST Configuration
Original Ć June 1990 CE4.2:CL6211
CASC CASC
(Continued from previous page)
OPERAND DESCRIPTIONS:
Loop tag - The tag name of the secondary loop in the cascade control system. The cascade
function will automatically recall the appropriate analog track value based on the mode of the
secondary loop.
Track overrides manual enable - When the primary loop is in manual mode, enabling this
parameter forces the output of the primary loop to track: 1) the process variable of the secondary
loop when the secondary loop is in manual, and 2) the set point of the secondary loop when the
secondary loop is in automatic. ENABLED or DISABLED can be specified.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = SVA(in)
SVD(out) = SVD(in)
Seitenansicht 132
1 2 ... 128 129 130 131 132 133 134 135 136 137 138 ... 319 320

Kommentare zu diesen Handbüchern

Keine Kommentare