4Ć30 FST Configuration
Original Ć June 1990CE4.2:CL6211
AAGM AAGM
(Continued from previous page)
CONFIGURATION FORMAT: AAGM (
Analog value >>
Eng conversion factors >>
Lower break point >>
Upper break point >>
Lower gain factor >>
Upper gain factor >>
Comment >>
OPERAND DESCRIPTIONS:
Analog value - The name of the general register or analog loadable function that contains the
adaptive gain signal.
Eng conversion factors - The name of the direct control point (DCP), indirect control point
(ICP), or auxiliary engineering unit pair that contains the engineering units high and low values.
Lower break point - A tuning parameter that specifies the value of the lower break point.
Break point values are -136 to 136 percent of engineering units span (in percent).
Upper break point - A tuning parameter that specifies the value of the upper break point.
Break point values are -136 to 136 percent of engineering units span (in percent).
Lower gain factor - A tuning parameter that indirectly determines the analog adaptive gain
below the lower break point (see Description section above). Gain factor values are 0.02 to 50.
Upper gain factor - A tuning parameter that indirectly determines the analog adaptive gain
above the upper break point (see Description section above). Gain factor values are 0.02 to 50.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If AGS < LBP
Then AAGF = 1 - [(1-LGF)X((LBP-AGS)/10)]
If LBP <= AGS <= UBP
Then AAGF = 1
If AGS > UBP
Then AAGF = 1 - [(1-UGF)X((AGS-UBP)/10)]
(Continued on next page)