4Ć81FST Configuration
Original Ć June 1990 CE4.2:CL6211
FFR FFR
(Continued from previous page)
TRUTH TABLE:
SVD(in)
0
1
0
1
SVD(out)Reset
0
0
1
1
Last SVD(out)
1
0
0
CONFIGURATION FORMAT: FFR (
Reset >>
Comment >>
OPERAND DESCRIPTIONS:
Reset - The name of the general register or discrete loadable function that contains the
discrete value.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If SVD(in) = 0 and Discrete Value = 0
Then SVD(out) = Last SVD(out)
If SVD(in) = 1 and Discrete Value = 0
Then SVD(out) = 1
If SVD(in) = 0 and Discrete Value = 1
Then SVD(out) = 0
If SVD(in) = 1 and Discrete Value = 1
Then SVD(out) = 0
SVA(out) = SVA(in)