5Ć1Configuration Tips
Original Ć June 1990 CE4.2:CL6211
5 Configuration Tips
5.1 Targeting Points
The ENVOX workstation makes target information part of the source
point. This allows a point to be targeted to multiple devices without
entering the target data multiple times, but will still allow different target
parameters for different devices if desired.
This is accomplished through the use of Target Groups. A target group
is a list of target devices for a point, PROVUEs, UOCs, CHIPs and Trend
Units, which share the same target definition (reporting parameters, etc.).
This prevents the need for multiple entry of the same data if the target
parameters are the same for more than one device.
For example, consider a point that is targeted to 2 PROVUEs and a CHIP,
all with change-of-state reporting, 0.5% dead zone, and 3 a second
sample interval. These would all be targeted by creating one target
group with those parameters, plus all the other PROVUEĆspecific
parameters such as extended alarms, message suppress, etc. The
appropriate information for those three devices (the target group), which
are going to share target parameters, is entered on the Target Data
device list.
Now assume the same point is to be targeted to three other PROVUEs
with exception reporting, 0.125% dead zone, and a 1 second sample
interval. The targeting would be accomplished by creating another target
group with these parameters, and entering the list of device names.
The target parameters may be different for each device if desired. In a
worstĆcase scenario, where all devices that are to be targeted have
different target parameters, a different target group would be created for
each target device.
To target a point, select the Target!" menu option to access the Target
Data form. This form has fields for entering most of the target
parameters, plus a group field where a list of target devices can be
entered. The list of devices actually shows all the devices the point is
targeted to, with the devices in the current group being identified by the
word YES in the Current?" field.
To look at a different target group select the Next!" menu option. This
will display a different set of parameters, and a different list of devices will
be marked Current". To create a new target group, select New!" and
enter the new data.
Notice that not all of the PROVUE target parameters are on the Target
Data form(e.g. message suppress, unit point, etc). They are accessed
Seitenansicht 262