5-16 Controller Cards
UM4.6:CS6003 Original — December 1991
Step 18: Press both of the lit MUX DI/DO CONTROLLER DI data
switches again to switch them OFF. The > 1 ACTIVE indicator
goes out and the NONE ACTIVE indicator of the DI STATUS
indicators lights. If the NONE ACTIVE indicator fails to light or
if another DI STATUS indicator lights, the configurable
controller requires repair.
Step 19: Disconnect the voltmeter.
Step 20: Set the calibrator ON/OFF switch to OFF.
Step 21: Disconnect the cable (if one is present) and remove the
configurable controller card. Replace the selector plug if
necessary.
5.4 Type CL6202 Computing Controller Card
This calibration procedure for the computing controller allows the user to
calibrate the 0 percent (ZERO) and 100 percent (SPAN) voltage levels of
the analog-to-digital conversion circuit. It also allows the measurement of
the 0 percent and 100 percent values of the analog current output and
the adjustment of the 100 percent analog current output. The procedure
tests the discrete inputs and outputs on the computing controller.
5.4.1 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltmeter
X00822–A
R44 Zero AdjustmentR45 Span AdjustmentR61 Span Current Output
Figure 5-10. Type CL6202 Computing Controller Unit