4-22 Input and Output Cards
UM4.6:CS6003 Original — December 1991
Step 5: Press the calibrator MUX switch. The calibrator numerical
display shows one of the following:
No Code — The card requires repair; terminate procedure
and obtain a replacement card
0005 — The card is a discrete input card; continue
procedure
Any Other Code — The card is not a discrete input card
or the card requires repair; terminate procedure and
obtain a replacement card
Step 6: Press the calibrator DI group mode switch.
Step 7: Connect one end of the 400 ohm resistor to the positive
breakout terminal for channel 1, listed in Table 4-11.
Table 4-11. Calibrator Breakout Terminal Assignments for
High-Voltage Discrete Input Cards
Breakout Terminal Function
1 Channel 1 +
2 Channel 1 –
3 Channel 2 +
4 Channel 2 –
5 Channel 3 +
6 Channel 3 –
7 Channel 4 +
8 Channel 4 –
9 Channel 5 +
10 Channel 5 –
11 Channel 6 +
12 Channel 6 –
13 Channel 7 +
14 Channel 7 –
15 Channel 8 +
16 Channel 8 –
17 +24 volts
18 +24 volts
19 24 volt return
20 24 volt return
Step 8: With the voltage source turned off, connect the positive lead
of the voltage source to the other end of the 400 ohm resistor
and the negative lead to the negative breakout terminal for
channel 1, listed in Table 4-11.
Step 9: Connect the voltmeter across the voltage source.