4-16 Input and Output Cards
UM4.6:CS6003 Original — December 1991
4.1.4.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Millivolt Source
4.1.4.3 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the isolated low-level analog input card in the calibrator
test slot labeled MUX.
Step 3: Connect the umbilical cable labeled MUX DI/BREAKOUT
between the connector on the front of the isolated low-level
analog input card and the calibrator receptacle labeled
BREAK-OUT CONNECTOR.
Step 4: Turn the calibrator ON.
Step 5: Press the calibrator MUX switch. The calibrator numerical
display should show the card identification code
corresponding to the type of card being calibrated, as listed in
Table 4-8. Verify the card type and go to step 6.
If no card identification code appears, the isolated low-level
analog input card requires repair. If a card identification code
appears, but is in Table 4-8, then the card is not an isolated
low-level analog input card, or requires repair. In either case,
terminate the calibration procedure and obtain a replacement
card.
Table 4-8. Isolated Low-Level Analog Input Card Identification Codes
Card Type Range Identification Code
Millivolt input –10 to 70 mV 0016
Type J thermocouple
–60° to 640°F
0034
0° to 1400°F
0035
Type K thermocouple
0° to 2300°F
0036
0° to 1000°F
0037
Type T thermocouple
–300° to 600°F
2720
Type E thermocouple
–100° to 1600°F
3360
Type R thermocouple
0° to 3200°F
0040
Step 6: Press the calibrator A12 group mode switch.